Heat Loss of Steel Pipes
For various water temperatures and steam pressures
Heat loss W/m for fluid inside pipe
| Nominal bore |
mm |
Water |
Steam |
|
|
50°C |
60°C |
75°C |
100°C |
1 bar |
4 bar |
| ½ |
15 |
30 |
40 |
60 |
90 |
130 |
190 |
| ¾ |
20 |
35 |
50 |
70 |
110 |
160 |
220 |
| 1 |
25 |
40 |
60 |
90 |
130 |
190 |
270 |
| 1¼ |
32 |
50 |
70 |
110 |
160 |
230 |
330 |
| 1½ |
40 |
55 |
80 |
120 |
180 |
250 |
370 |
| 2 |
50 |
65 |
95 |
150 |
220 |
310 |
440 |
| 2½ |
65 |
80 |
120 |
170 |
260 |
360 |
530 |
| 3 |
80 |
100 |
140 |
210 |
300 |
440 |
630 |
| 4 |
100 |
120 |
170 |
260 |
380 |
550 |
800 |
| 6 |
150 |
170 |
250 |
370 |
540 |
770 |
1100 |
Heat loss Btu/h ft for fluid inside pipe
| Water |
Steam |
| 120°F |
140°F |
170°F |
212°F |
15 psig |
60 psig |
| 30 |
40 |
60 |
95 |
135 |
200 |
| 35 |
50 |
75 |
115 |
170 |
230 |
| 40 |
60 |
90 |
135 |
200 |
280 |
| 50 |
70 |
110 |
165 |
240 |
340 |
| 55 |
80 |
120 |
190 |
260 |
370 |
| 65 |
95 |
150 |
230 |
320 |
460 |
| 80 |
120 |
180 |
270 |
380 |
550 |
| 100 |
140 |
210 |
310 |
440 |
630 |
| 120 |
170 |
250 |
380 |
560 |
800 |
| 170 |
250 |
370 |
540 |
770 |
1100 |
Correction factors for use with above table
| Condition |
Factor |
| Single pipe along skirting or riser |
1.0 |
| More than one pipe along skirting or riser |
0.90 |
| Single pipe along ceiling |
0.75 |
| More than one pipe along ceiling |
0.65 |
| Single pipe freely exposed |
1.1 |
| More than one pipe freely exposed |
1.0 |
Heat Loss of Steel Pipes© - All Rights Reserved 2025